Phenix 440-20B DC Hipot Tester

No stress rentals! We help you to choose the equipment that you need, we expedite shipment, and follow up.

Phenix 440-20B DC Hipot Tester
  • Application

  • The Phenix 440-20B can generate 40 kV at 20 mA. It features a full-color touch-screen display, automatic control of the output voltage, and a communications port for for data acquisition.
  • Key features

  • 7in. full-color touch-screen display
  • Manual or automatic output voltage raise/lower
  • Auto-ranging Meter accuracy: ± (0.5% of reading +LSD)
  • Communications port for data acquisition
  • Insulation resistance calculation

Specifications
Electrical specifications
Input power 110 to 120 V, 5 A
220 to 240 V, 3 A
Input frequency 50/60 Hz
Output voltage ~ 0 to 40 kV, 20 mA
Ripple < 2%
Polarity Negative output, positive ground
Duty cycle Continuous capacitive charging: 20 mA
Internal discharge device 3 kJ
Auto ranging meter for voltage 4 digits displayed
Auto ranging meter for current 5 digits displayed
Cables included Input power: 7 ft (2 m)
High voltage: 20 ft (6 m)
Ground: 20 ft (6 m)
Return: 20 ft (6 m)
Physical specifications
Control section Dimensions: (L 18.5 x W 10.5 x H 21.5)in (470 x 267 x 546)mm
Weight: 50 lbs (23 kg)
Shipping dimensions (L 22 x W 14 x H 24)in (558 x 356 x 610)mm
Weight: 56 lbs (25 kg)
Operating temperature 10 to 40 °C, indoor/outdoor in fair weather
Humidity (operating) < 95% non-condensing
Altitude < 3300 ft (1000 meters)
For detailed specifications please see: Phenix 440-20B Data Sheet