Specifications, Applications, & Benefits
Applications |
Perform accurate DC Hipot testing of cables, electrical switchgear, motors, generators, and protective equipment |
Features and benefits |
- Field testing: This lightweight and rugged instrument delivers 120kV DC in the field with unmatched safety, accuracy, and ease of use.
- Safety:Safety features include instantaneous and thermal overload protection for operator and test object, shielded high voltage cable, solenoid operated discharge switch, and carefully designed grounding features.
- Accuracy:The high voltage is generated by a filtered doubler circuit, and precision metering measured off the high voltage output indicates the output voltage and leakage current on large easy-to-read digital meters. An analog meter is provided for reading the leakage current.
- Ease of use: With more than 35 years of manufacturing experience, Phenix Technologies makes instruments with well laid out panels that are intuitively easy to use, with large digital meters, convenient cable storage, and excellent instruction manuals. Setup time is minimal.
|
Input voltage |
110 to 120V, 10A, 50/60 Hz. (Please specify when placing order) 220 to 240V, 5A, 50/60 Hz. (Please specify when placing order) |
Output Voltage |
0 to 120kV DC |
Output Current |
10 mA |
Duty cycle |
Continuous capacitive charging: 10 mA |
Digital metering |
3½ digit, accuracy 0.5% of full scale |
Ripple |
Very low ripple: <2% RMS at full output |
Dimensions - Control Unit Dimensions - HV Tank |
21"L X 17"W X 14"H (533 X 432 X 355)mm 17.5"L X 12"W X 22"H (440 X 305 X 560)mm |
Weight - Control Unit Weight - HV Tank |
Net weight: 33 lbs (15 kg) Net weight: 111 lbs (50 kg) |
Shipping container |
Dimensions: 48"L X 30"W X 31"H (1219 X 762 X 787)mm Weight: 195 lbs (88 kg) |
Cables and documentation |
- Input Line Cord, 7 ft.
- Return Cable, 20 ft.
- High Voltage Cable, 20 ft.
- Ground Cable, 20 ft.
- Power Interconnect, 25 ft.
- Calibration Certificate
- Operation/Maintenance Manual, 2 copies
|
Optional items |
- Ground Stick: Model GS100-2 (100kV), or GS160-2 (160kV). 2-piece design with a 25 ft. Ground Lead
- Discharge Stick: Model DS100-2 (100kV, 100kΩ, 50kJ). 2-piece design with a 25 ft. Ground Lead
- Safety Foot Switch with 20 ft. lead
- Positive polarity output
- Custom cable lengths
- Calibration Certificate with data
|