No stress rentals! We help you to choose the equipment that you need, we expedite shipment, and follow up.
Bridge circuit | Transformer ratio arm bridge |
---|---|
Capacitance | Range: 12 multipliers are used to allow measurements from less than 20 pF to 1.2 μF Accuracy: ±0.25% of range ±4 pF |
Detector | Synchronous, tuned and phase-sensitive null detector |
Test voltage | 28 V, 100 Hz for 60 Hz test set 28 V, 80 Hz for 50 Hz test set |
Measurements | UST CH-L (ungrounded specimen test, HI to LO) GST CH-G (grounded specimen test,HI to ground, LO guard) GST CL-G (grounded specimen test,LO to ground, HI guard) GST CH-G + CH-L (grounded specimen test, HI to ground, plus HI to LO) GST CL-G + CL-H (grounded specimen test, LO to ground, plus LO to HI) |
Input power (must specify) | 120 V, 60 Hz, 5 VA or 240 V, 50 Hz, 5 VA or 220 V, 60 Hz, 5 VA |
Dinensions | 10.3 H x 11.3 W x 8.5 D in. 262 H x 287 W x 216 D mm |
Weight | 14 lb (6.5 kg) |
Shipping weight | 36 lb (16.5 kg) |