Channels | 1 |
---|---|
Frequency range | 10 Hz to 25 MHz |
Output voltage | 20 V peak-to-peak at 50 Ω |
Output protection | Short circuit protected |
Source impedance | 50 Ω |
Channels | 2 |
---|---|
Sampling | Simultaneous |
Frequency range | 10 Hz to 25 MHz |
Max. sampling rate | 10 MS/s |
Input impedance | 50 Ω |
Test method | Sweep frequency |
---|---|
PC Comm | Ethernet USB/Serial |
Frequency range | 10 Hz to 25 MHz |
Number of points | 1000 points (Default) Up to 1800 points (Extended Range) |
Point spacing | 1.2% Logarithmic |
Dynamic range | > 90 dB |
Repeatability | ±1 dB to -80 dB |
IF bandwidth | < 10% of active frequency |
Scaling | Linear/Log |
---|---|
Frequency range | 10 Hz to 25 MHz, user defined within frequency range |
Plotting | Frequency vs. Magnitude/Phase |
Analysis | Difference, sub-band cross-correlation |
Dimensions | 18.2 x 13.4 x 6.7 inch 46.2 x 34.0 x 17.0 cm |
---|---|
Weight | 13.1 lbs (6.0 kg) |
Power supply | 100 to 240 VAC |
Temperature | 0° to 50°C operating -25° to 70°C storage |
Relative humidity | 0% to 95% non condensing |
Test Leads construction | Integrated three lead system in single cable set Standard (362 kV and below): 60 ft/ 18 m Optional (> 362 kV): 100 ft/ 30 m |