TES-3600 3-Phase Power & Harmonics Analyzer

TES-3600 3-Phase Power & Harmonics Analyzer
  • Features & specifications

  • Easy-to-View 10-Display LCD Screen
  • 4 1000A CTs included
  • True RMS Sensing
  • Power KW, KVAR, KVA, PF, θ, Hz
  • Energy: KWh, KVARh & KVAh measurement
  • Phase sequence indicator function
  • 4GB SD Card for data storage
  • USB Interface and Windows™ Software
  • Easy-to-use Push Button Operation
  • Price: $1395.00 US dollars

Voltage measurement (V)
Range Resolution Accuracy Input Impedance Overload Protection
999.9V 0.1V ±(0.3% rdg ±10dgts) (>10V) 2MΩ 1000Vrms

Trms AC Current Measurement (A) Autoranging
Range Resolution Accuracy
(including current probe)
Current Probe output Overload Protection
999.9A 0.1A ±(0.5% rdg ±10dgts) (>10A) 0.35mV/A 1000Arms

Active Power measurement (kW)
Range Resolution Accuracy
999.9kW 0.1kW ±(1.0% rdg ±20dgts)

Reactive Power measurement Q (KVAR)
Range Resolution Accuracy
999.9kVAR 0.1kVAR ±(1.0% rdg ±20dgts)

Apparent Power measurement S (KVA)
Range Resolution Accuracy
999.9kVA 0.1kVA ±(1.0% rdg ±20dgts)

Power Factor measurement (Cos ψ)
Range Resolution Calculated Accuracy
-1 ~ +1 0.001 ±10dgts

Phase Angle measurement (ψ)
Range Resolution Calculated Accuracy
+180° ~ 0° ~ -180° 0.1° ±15dgts

Frequency measurement (Hz)
Range Resolution Accuracy
60 Hz 0.1 Hz ±1% ±2dgts

General Specifications
Dimensions (L x W x H): (9.3 x 4.6 x 2.1)in.; (235 x 116 x 54)mm
Operating Temperature and Humidity 0° C to 50° C (32°: F to 122°: F); RH < 80% non-condensing
Storage Temperature and Humidity -10° C to 60° C (14°: F to 140°: F); RH < 70% non-condensing
Accessories Instruction manual, Software CD-ROM, Optical USB interface, Deluxe carrying case, Batteries, AC adaptor (110V AC to 12V DC; or 220V AC to 12V DC), 4 1000A CTs (with 42mm jaw opening and 3-meter leads), 4 voltage leads with crocodile clips and 3-meter leads.