| AC Voltage input range | 90 to 264 V rms, 50/60 Hz, 100VA |
|---|---|
| Battery | 1.1 V, 5.2Ah meets IEC 62133:2003 |
| Battery life | 4.5 hours (typical) continuous testing at 10 kV with a 100 MΩ load |
| Battery charge time | 2.5 hours deep discharge, 2 hours normal discharge |
| 30 min quick charge | 1 hour operation at 5 kV with a 100 MΩ load |
| Resistance range | 10 kΩ to 15 TΩ @ 5 kV, 10 kΩ to 35 TΩ @ 10 kV |
| Analog display range | 100 kΩ to 10 TΩ |
| Digital display range | 100 kΩ to 35 TΩ |
| Timer range | Up to 99 minutes 59 seconds, 15 second minimum setting |
| Memory capacity | 11 hrs logging @ 5 sec intervals |
| Test modes | IR, IR(t), DAR, PI, SV, DD, ramp test |
| Interfaces | USB type B (device), Bluetooth® Class 2 |
| Real time output | (V, I, R) readings at a rate of 1 Hz |
| Remote control | Remote control via USB cable only (requires RC dongle to be in position) |
| Altitude | 3000 m |
| Operating temperature | -20 °C to 50 °C |
| Ingress protection | IP65 (lid closed), IP40 (lid open) |
| Safety | Meets the requirements of IEC 61010-1, CATIV 600V to 3000 m |
| EMC | Meets the requirements of IEC61326-1 |
| Dimensions | 285 mm x 181 mm x 315 mm |
| Weight | 4.5 kg |