Hipotronics 7BT60 Series Vacuum Interrupter Test Set

No stress rentals! We help you to choose the equipment that you need, we expedite shipment, and follow up.

Hipotronics 7BT60 Series Vacuum Interrupter Test Set
  • Features & specifications

  • Automatic testing
  • Dwell Timer
  • Memory Kilovoltmeter
  • Pre-programmable Output Kilovoltmeter
  • Failure indicator Lamp
  • 500 or 3000 V/sec Rise Time
  • Removable High Voltage Section for operator safety
  • Field proven reliability
  • Go, No-Go Test with a PASS/FAIL indicator lamp
  • Minimum setup time for quick testing
  • Self-contained: single-piece unit suitable for field use

General Specifications
Testing process The 7BT60 tests the integrity of vacuum interrupters in switchgear by generating an output current that is programmed to raise voltage at a preset rate to the desired test level. Once the unit reaches the preset voltage a dwell timer holds the voltage at that level for the preset duration. Any failure is indicated on the failure lamp on the front panel and the breakdown voltage is indicated on the Memory kV meter.
Input Voltage & Frequency Model 7BT60-A for 120V/60Hz input
Model 7BT60-B for 230V/50Hz input
System output 0 - 60 kV (center tapped)
20 mA
Rise Time 500 V/s or 3000 V/s
Dimensions 12"W x 34"H x 12"D
Weight Net weight: 96 lbs.
Shipping weight: 125 lbs.
Included with 7BT60
  • 25 ft. Interconnect Cable between controller and base
  • 10 ft. Test Leads, qty. 2
  • 6 ft. Input Power Cord
  • User's Manual
  • Calibration Certificate